Powerware

check_xups_alarm

Description:

This 2 plugins for completly check PowerwWare UPS.

check_xups_alarm:

This plugin checks the active UPS alarms comparing them with both warning and critical alarm lists.
It`s plugin rewrited and for PowerWare UPS (XUPS-MIB) from this
http://exchange.nagios.org/directory/Plugins/Hardware/UPS/check_ups_alarms/details

check_ups_pw.sh:
Parser for check_snmp plugin (need XUPS-MIB)

Recent change:
check_ups_pw.sh (0.51): Add 255C bug catcher for xupsEnvAmbientTemp.0

Current Version

0.51

Last Release Date

2011-09-25

Compatible With

  • Nagios 3.x

Owner

License

GPL


Nagios CSP

Meet The New Nagios Core Services Platform

Built on over 25 years of monitoring experience, the Nagios Core Services Platform provides insightful monitoring dashboards, time-saving monitoring wizards, and unmatched ease of use. Use it for free indefinitely.

Monitoring Made Magically Better

  • Nagios Core on Overdrive
  • Powerful Monitoring Dashboards
  • Time-Saving Configuration Wizards
  • Open Source Powered Monitoring On Steroids
  • And So Much More!
Project Files
Project Notes
define command{ command_name ups_bat_cap command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsBatCapacity.0 -l 'Battery capacity' -w 90 -c 20 } define command{ command_name ups_bat_sec command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o mib-2.33.1.2.2.0 -l 'Battery Runtime' -u 'sec' } define command{ command_name ups_bat_volts command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsBatVoltage.0 -l 'Battery Voltage' -u 'Volts' } define command{ command_name ups_model command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsIdentModel.0 } define command{ command_name ups_in_volts command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsInputVoltage.1 -l 'Input Voltage' -u 'Volts' } define command{ command_name ups_out_load command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsOutputLoad.0 -l 'The UPS output load in percent of rated capacity' -u '%' } define command{ command_name ups_out_walts command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsOutputWatts.1 -l 'The measured real output power' -u 'Watts' } define command{ command_name ups_tem_input command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsEnvAmbientTemp.0 -l 'Input temp' -u 'C' -w 38 -c 40 } define command{ command_name ups_tem_remote command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsEnvRemoteTemp.0 -l 'Output temp' -u 'C' -w 28 -c 30 } define command{ command_name ups_bat_test command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsTestBatteryStatus.0 -l 'Battery test' -w 2 -c 2 } define command{ command_name ups_humidity command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsEnvRemoteHumidity.0 -l 'Humidity' -u '%' -w 80 -c 90 } define command{ command_name ups_alarm command_line $USER1$/check_xups_alarms.pl -H $HOSTADDRESS$ -E1 -w 1..41 -c 3,4,7..16,23,26,27,29,31..36,39 }
Reviews (0) Add a Review
Add a Review

You must be logged in to submit a review.

Thank you for your review!

Your review has been submitted and is pending approval.

Recommend

To:


From:


Thank you for your recommendation!

Your recommendation has been sent.

Project Stats
Rating
0 (0)
Favorites
0
Views
95,828