Powerware

check_xups_alarm

Description:

This 2 plugins for completly check PowerwWare UPS.

check_xups_alarm:

This plugin checks the active UPS alarms comparing them with both warning and critical alarm lists.
It`s plugin rewrited and for PowerWare UPS (XUPS-MIB) from this
http://exchange.nagios.org/directory/Plugins/Hardware/UPS/check_ups_alarms/details

check_ups_pw.sh:
Parser for check_snmp plugin (need XUPS-MIB)

Recent change:
check_ups_pw.sh (0.51): Add 255C bug catcher for xupsEnvAmbientTemp.0

Current Version

0.51

Last Release Date

2011-09-25

Compatible With

  • Nagios 3.x

Owner

License

GPL


Project Files
Project Notes
define command{ command_name ups_bat_cap command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsBatCapacity.0 -l 'Battery capacity' -w 90 -c 20 } define command{ command_name ups_bat_sec command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o mib-2.33.1.2.2.0 -l 'Battery Runtime' -u 'sec' } define command{ command_name ups_bat_volts command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsBatVoltage.0 -l 'Battery Voltage' -u 'Volts' } define command{ command_name ups_model command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsIdentModel.0 } define command{ command_name ups_in_volts command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsInputVoltage.1 -l 'Input Voltage' -u 'Volts' } define command{ command_name ups_out_load command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsOutputLoad.0 -l 'The UPS output load in percent of rated capacity' -u '%' } define command{ command_name ups_out_walts command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsOutputWatts.1 -l 'The measured real output power' -u 'Watts' } define command{ command_name ups_tem_input command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsEnvAmbientTemp.0 -l 'Input temp' -u 'C' -w 38 -c 40 } define command{ command_name ups_tem_remote command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsEnvRemoteTemp.0 -l 'Output temp' -u 'C' -w 28 -c 30 } define command{ command_name ups_bat_test command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsTestBatteryStatus.0 -l 'Battery test' -w 2 -c 2 } define command{ command_name ups_humidity command_line $USER1$/check_ups_pw.sh -H $HOSTADDRESS$ -o xupsEnvRemoteHumidity.0 -l 'Humidity' -u '%' -w 80 -c 90 } define command{ command_name ups_alarm command_line $USER1$/check_xups_alarms.pl -H $HOSTADDRESS$ -E1 -w 1..41 -c 3,4,7..16,23,26,27,29,31..36,39 }
Reviews (0) Add a Review
Add a Review

You must be logged in to submit a review.

Thank you for your review!

Your review has been submitted and is pending approval.

Recommend

To:


From:


Thank you for your recommendation!

Your recommendation has been sent.

Project Stats
Rating
0 (0)
Favorites
0
Views
95,798