Sample Code for communication to APC UPS Via: SNMP / Link to Text File

Current Version

Last Release Date

2009-08-19

Compatible With

  • Nagios 1.x
  • Nagios 2.x
  • Nagios 3.x

Owner


Project Photos
Project Notes
After Weeks of searching....Finally Source code in Text File - download Hope it helps. Jeff
Reviews (6) Add a Review
Very useful - with critical flaw
by asa1, March 31, 2014

This example is extremely useful, but the author doesn't seem to understand the crazy way the check_snmp plugin defines critical and warning ranges. For example, the latesttest_result SNMP value is 2 if failed, 1 if passed. The -c 2 flag means anything GREATER than 2 is critical, so a status of 2 passed, when it should not. The correct syntax should be -c 1. This also affects the snmp_ups_stat check for the main battery status, which I believe should probably use a -c 2 flag, with no warning flag based on this description in the MIB: "The status of the ups batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition." It's very unfortunate that the check_snmp works this way, since it makes reading and writing these checks very counter intuitive. I want to stress that I'm very grateful for all the work the author of this check - it's saved me a huge amount of time, despite these small but important mistakes.



Zero Effort Plugin for APC UPS
by nishith, January 31, 2013

Very easy to setup. Also, I would like to know what is the mean of "UPS Status". Is it possible to get "Email/SMS" alerts for below states. ALERT Report(Email/SMS) if UPS is on Battery Power ALERT Report(Email/SMS) if UPS is on AC Mains Power Presently, my "UPS Status" STATE shows "SNMP OK-Main UPS Status 2". What does it mean?



Need net-snmp help
by kibosh, October 31, 2012

I am unable to find net-snmp-5.3.3.pre1.tar.gz on sourceforge. All the net-snmp projects hosted on sourceforge seem to have an .exe file extension. Please advise. Thank you.



It works.
by matthew, July 31, 2012

Working well with our Smart-UPS RT 5000 XL, thank you very much for submitting your work.



Awesome
by devcon, April 30, 2012

the only working solution without any additional dameon software, works great for APC network managment cards. Just one small typo: "Output Voltage" should be "Input Voltage" on the following command definition: # 'snmp_ups_voltage_in' command definition define command{ command_name snmp_ups_voltage_in command_line $USER1$/check_snmp -H $HOSTADDRESS$ -C $ARG1$ -o .1.3.6.1.4.1.318.1.1.1.3.2.1.0 -l 'Output Voltage' -u 'Volts' }



Good list - although no plugin very helpful
by Napsty, March 31, 2012

Thanks for putting together this list. Although this isn't a plugin but a list of OID's it was actually more helpful than other APC plugins lying around here (most of them don't work or need addditional software).